⚡ Perhitungan Voltage Rectifier
Kalkulator untuk menentukan tegangan kerja trafo rectifier sistem ICCP menggunakan Dwight Equation
Parameter Input Sistem
Kebutuhan Arus (Ampere)
Panjang Kabel ke Trafo (meter)
Luas Penampang Kabel (mm²)
10 mm²
16 mm²
25 mm²
35 mm²
50 mm²
70 mm²
Soil Resistivity (Ω.m)
10 Ω.m (Wet soil - Tanah basah)
20 Ω.m (Moist soil - Tanah lembab)
50 Ω.m (Dry soil - Tanah kering)
100 Ω.m (Rocky soil - Tanah berbatu)
Panjang Sumur Anode (meter)
Diameter Sumur Anode (inch)
6 inch (150 mm)
8 inch (200 mm)
10 inch (250 mm)
Hitung Voltage Rectifier
Langkah Perhitungan
Resistansi Sumur Anode
Dwight Equation:
R = ρ / (2 × π × L) × [ln(4L / d) - 1]
Dimana:
ρ = soil resistivity (Ω.m)
L = panjang sumur anode (m)
d = diameter sumur anode (m)
Resistansi Kabel
Resistansi Kabel Tembaga:
R = (ρ × L) / A
Pada suhu operasi 90°C (XLPE max):
ρ_copper ≈ 0.0232 Ω.mm²/m
Tegangan Kerja Rectifier
V = I × R_total
R_total = R_anode + R_cable
Dengan safety factor 25%:
V_kerja = V × 1.25
Catatan Teknis
Standar & Referensi
IEC 60228:
Standar resistansi kabel tembaga
Dwight Equation:
Perhitungan resistansi elektroda batang vertikal
NACE SP0169:
Standar sistem proteksi katodik
Safety Factor 25%:
Margin keamanan untuk variasi kondisi lapangan
Asumsi Perhitungan
Kabel tembaga dengan isolasi XLPE
Suhu operasi maksimal 90°C
Sumur anode vertikal dengan backfill
Kondisi tanah homogen